Potter Electric Signal IDC-6 EXPANDER / PFC-4064

SKU : IDC-6 Category

The IDC-6 is connected to the fire control panels using a 4-wire RS485 connection. The connection is power limited and supervised. The IDC-6 must be mounted in either a compatible fire alarm panel, the PSN-1000, or within 20 feet of the panel or power supply using the AE-2, AE-8, or the AE-14 expander cabinet. Each card is mounted to the exclusive Stacker Bracket for secure and accessible mounting.

Potter Electric Signal IDC-6 EXPANDER / PFC-4064

The Initiating Device Circuit Expander (IDC-6) provides an additional 6 inputs per module. The panel supports up to thirty-one (31) IDC-6 modules. The circuits are power-limited and supervised. All inputs are suitable to monitor 2-wire smoke detectors. Smoke detectors shall be installed in compliance with NFPA 72. Inputs can also be used for automatic, manual, waterflow or supervisory service. The IDC-6 communicates via the PLink communication bus. The IDC-6 can be mounted in either the control panel cabinet, the intelligent power supply, AE-2, AE-8 or the AE-14 expander cabinet. Each card is mounted to the exclusive Stacker Bracket for secure and accessible mounting.

Features:

  • Mounts with included stacker bracket
  • May mount in panel, accessory cabinet, AE-2, AE-8 or AE-14 Accessory Cabinets or the PSN-1000/E Power Supply
  • Provides 6 IDC Input Circuits
  • Maximum 31 IDC-6 per panel
  • Maximum P-Link wire length of 20 feet
Brand

Supplier

Reviews

There are no reviews yet.

Be the first to review “Potter Electric Signal IDC-6 EXPANDER / PFC-4064”

Your email address will not be published. Required fields are marked *

IDC-6 Specification Sheet

Download

IDC-6 Installation Manual

Download